Q:  Does Microlite® duct wrap comply with ASTM C 553?


A:  Microlite® duct wrap falls under the very broad Scope of ASTM C 553, Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications. Microlite® duct wrap complies with all requirements of ASTM C 553 Types I, II and III except maximum use temperature. ASTM C 553 sets a maximum use temperature of 450°F for Types I, II and III. Johns Manville sets a maximum use temperature of 350°F for unfaced Microlite® duct wrap and 250°F for faced Microlite® duct wrap.

Compliance with ASTM C 553, except maximum use temperature
 
Type I
Type II
Type III
R-Series Microlite®
yes
yes
 
Type 75 Microlite®
yes
yes
 
Type 100 Microlite®
yes
yes
 
Type 150 Microlite®
yes
yes
yes

 
The current ASTM specification specifically for duct wrap is C 1290, Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts. It indicates a maximum use temperature of 250°F.